Explosion Proof Enclosure Manufacturers | Stainless Steel Explosion Proof Enclosure

Explosion Proof Enclosure Manufacturers | Stainless Steel Explosion Proof Enclosure

The explosion-proof principle is that when an explosion occurs in the explosion-proof casing, the flame generated by the explosion is extinguished when passing through the explosion-proof surface, and the gas outside the casing cannot be detonated.
Obter uma citação
Quem somos

Temos as melhores soluções para o seu negócio

Yueqing Chuanwang Electric Technology Co., Ltd. foi criada em 2014, a empresa está localizada na bela e rica cidade de Liushi, Yueqing City, a capital elétrica da China.

Após mais de 10 anos de luta, a empresa tornou-se uma empresa de entidade nacional não regional hoje, e sua rede de vendas abrange todas as províncias e cidades em todo o país, bem como o Oriente Médio, Leste Asiático e América do Norte. Atualmente, o grupo tem mais de 200 funcionários e agora se desenvolveu em uma empresa não regional diversificada, integrando pesquisa e desenvolvimento de produtos, design, produção, operação e serviço. A área total da oficina da empresa é de 15.000 metros quadrados, o valor total dos ativos é de cerca de 100 milhões de yuans e a capacidade de produção anual é de 200 milhões de yuans. Empresas de apoio profissional para ventiladores, aparelhos elétricos à prova de explosão, iluminação móvel, iluminação fixa e outros produtos da série, fornecedores de alta qualidade de produtos de suporte à prova de explosão, como PetroChina, Sinopec, China Coal, etc. Parceiro ideal para conservação de água, governo e outras unidades.

A empresa obteve uma série de produtos "Certificado à Prova de Explosão", "Licença Industrial Nacional", "Certificação de Segurança do Carvão", "Certificação 3C" e passou na "Certificação do Sistema de Qualidade ISO9001:2008" e na certificação FM/UL dos Estados Unidos, ATEX da União Europeia, IECEx Internacional, Certificação de padrão de qualidade internacional, como a certificação Rússia TR e Brasil Inmetro. Também melhoramos continuamente a qualidade do produto e expandimos novas especificações para atender a diferentes requisitos.

Saiba Mais

Fasteners on the shell of explosion-proof explosion-proof distribution box

1. The fasteners should have sufficient mechanical strength, and when the shell explodes, it will not cause the bolts to break;
2. The fasteners should have anti-rust and anti-loosening measures to ensure the clearance of the plane flameproof joint surface;
3. When tightening with bolts, if the spring washer is used to prevent loosening, it is only necessary to flatten the spring washer, and it is not advisable to tighten it too tightly;
4. In order to avoid the shearing of the fastening bolts by external force, the dimensions of the joint of the cover and the shell must be consistent;
5. In order to fasten firmly, it is not allowed to use plastic or light alloy to make bolts and nuts, and it is not allowed to tap the screw holes directly on the plastic shell;
6. The depth of the impermeable screw holes should ensure that after the bolts and screw holes are fastened, there must be a thread allowance greater than 2 times the thickness of the anti-loose washers;
7. The thickness of the periphery and bottom of the impermeable screw hole shall not be less than one-third of the diameter of the bolt, but there shall be a margin of at least 3.0mm;
8. Process through holes or screw holes that must penetrate the shell in structure should be blocked by cylindrical or threaded flameproof structures, and the exposed ends must be permanently fixed.

Fasteners on the shell of explosion-proof explosion-proof distribution box

Transparent parts on the shell of explosion-proof explosion-proof distribution box

1. Transparent parts are mainly used for transparent covers of lighting fixtures, instrument windows, indicator covers and other parts;
2. The transparent cover of the lighting fixture is made of tempered glass and high boron glass;
3. The transparent parts used in the instrument window are made of optical glass and tempered glass. The former has good transparency, but the thickness should be increased;
4. The transparent parts for the indicator light cover are made of tempered glass and polycarbonate plastic;
5. The above should be able to withstand the specified impact test and pressure test;
6. There are two methods of fixing transparent parts on the flameproof shell: adhesive type and liner type;
7. The width of adhesive or pad should meet the requirements of 2 relevant regulations.

Interlocking device and warning plate on the shell of explosion-proof explosion-proof distribution box

1. The explosion-proof distribution box that will generate sparks and arcs during normal operation must be equipped with an interlocking device;
2. The mechanism of the interlocking device should ensure that the cover cannot be opened when the power is turned on;
3. After the cover is opened, the power supply cannot be turned on;
4. The shell fastened with bolts is allowed to replace the interlocking device with a warning sign.

Interlocking device and warning plate on the shell of explosion-proof explosion-proof distribution box
Pergunta frequentemente feita

Você tem alguma pergunta?

Explosion proof, according to the National Electrical Code, applies to an apparatus enclosed in a case that is capable of withstanding a gas or vapor explosion. It means that, should there be an explosion, it will be contained within an enclosure.

Intrinsically safe enclosures are designed to limit the current, voltage, power and temperature of the circuits. As such, there is insufficient power in an intrinsically safe enclosure that could cause a spark or an ignition in an explosive atmosphere.

There is no difference except term. Flameproof design is one of the explosion protection technique extensively used for light fittings, JBs, motors in hazardous areas.